General |
User Interface |
Graphical LCD with blue backlight and text in English, French, German, Portuguese, Italian and Spanish |
LEDs |
Four status-indicating LEDs |
Topology |
Double-conversion |
Diagnostics |
Full system self-test |
UPS Bypass |
Automatic bypass |
Dimensions |
See model selection guide |
Rail Kit |
Included with all units |
Electrical Input |
Nominal Voltage |
230V (208V, 220V, 230V, 240V and 250V user-selectable) |
Voltage Range |
156–280 Vac (output PF 0.7) |
Power Draw of UPS (full load) |
5000 VA: 21.7A @230V 6000 VA: 26.0A @208V |
Recommended Input Breaker Rating |
35A |
Frequency |
50/60 Hz autoselect |
Frequency Range |
40–70 Hz |
Electrical Output |
Power Factor |
0.7 |
On Utility Voltage Regulation |
±2% of nominal |
On Battery Voltage Regulation |
±2% of nominal |
Efficiency |
>97% in high-efficiency mode; 91% in normal mode |
Frequency Regulation |
±3% Hz online |
Load Crest Factor |
3 to 1 |
Battery |
Internal Battery Type |
5.5 Ah, sealed, lead-acid; maintenance free |
External Battery Modules |
Up to four per 9135, rail kits included for rack mounting |
EBM Battery Type |
5.5 Ah, sealed, lead-acid; maintenance free |
Battery Runtime |
Four (4) minutes with internal batteries @100% load (0.7 PF) For additional details, see battery runtime chart |
Battery recharge time |
Six (6) hours to recover 90 percent of nominal backup time after 100 percent RCD load discharge |
Battery Replacement |
Hot-swappable internal and external batteries |
Start-On-Battery |
Allows start of UPS without utility input |
Communications |
Serial Port |
RS-232 as standard, RS-232 cable provided |
USB Port |
As standard (HID) |
Relay Output |
DB-9 Dry Contact—common alarm as standard |
Communications Slot |
Optional communication slots (MS-Slot) |
Software |
LanSafe UPS monitoring and management software |
Environmental |
Safety Markings |
CE, C-Tick, UL, GS |
EMC Markings |
IEC/EN 62 040-2 class A |
Audible Noise |
Max 46 dB |
Ambient Operating |
0˚C to +40˚C |
Storage Temperature |
-20˚C to +40˚C with batteries and -25˚C to +55˚C without batteries |
Relative Humidity |
5–90% non-condensing |